CVE-2025-9041

Summary

A security issue exists due to improper handling of CIP Class 32’s request when a module is inhibited on the 5094-IF8 device. It causes the module to enter a fault state with the Module LED flashing red. Upon un-inhibiting, the module returns a connection fault (Code 16#0010), and the module cannot recover without a power cycle.

Affected Software

VendorProductVersion RangeStatus
Rockwell AutomationFLEX 5000 I/OVersion 2.011 or belowaffected

Weaknesses

  • CWE-1287: CWE-1287: Improper Validation of Specified Type of Input

ADP Enrichment

CISA ADP Vulnrichment

  • SSVC:
  • Exploitation: none
    • Automatable: yes
    • Technical Impact: partial

References