CVE-2025-40944

Summary

A vulnerability has been identified in SIMATIC ET 200AL IM 157-1 PN (6ES7157-1AB00-0AB0) (All versions), SIMATIC ET 200MP IM 155-5 PN HF (6ES7155-5AA00-0AC0) (All versions >= V4.2.0), SIMATIC ET 200SP IM 155-6 MF HF (6ES7155-6MU00-0CN0) (All versions), SIMATIC ET 200SP IM 155-6 PN HA (incl. SIPLUS variants) (All versions < V1.3), SIMATIC ET 200SP IM 155-6 PN R1 (6ES7155-6AU00-0HM0) (All versions < V6.0.1), SIMATIC ET 200SP IM 155-6 PN/2 HF (6ES7155-6AU01-0CN0) (All versions >= V4.2.0 < V4.2.5), SIMATIC ET 200SP IM 155-6 PN/3 HF (6ES7155-6AU30-0CN0) (All versions < V4.2.2), SIMATIC PN/MF Coupler (6ES7158-3MU10-0XA0) (All versions), SIMATIC PN/PN Coupler (6ES7158-3AD10-0XA0) (All versions < V6.0.0), SIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-2AC0) (All versions >= V4.2.0), SIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-7AC0) (All versions >= V4.2.0), SIPLUS ET 200MP IM 155-5 PN HF T1 RAIL (6AG2155-5AA00-1AC0) (All versions >= V4.2.0), SIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU01-2CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU01-7CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS ET 200SP IM 155-6 PN HF T1 RAIL (6AG2155-6AU01-1CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS ET 200SP IM 155-6 PN HF TX RAIL (6AG2155-6AU01-4CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS NET PN/PN Coupler (6AG2158-3AD10-4XA0) (All versions < V6.0.0). Affected devices do not properly handle S7 protocol session disconnect requests. When receiving a valid S7 protocol Disconnect Request (COTP DR TPDU) on TCP port 102, the devices enter an improper session state.

This could allow an attacker to cause the device to become unresponsive, leading to a denial-of-service condition that requires a power cycle to restore normal operation.

Affected Software

VendorProductVersion RangeStatus
SiemensSIMATIC ET 200AL IM 157-1 PN0 < *affected
SiemensSIMATIC ET 200MP IM 155-5 PN HFV4.2.0 < *affected
SiemensSIMATIC ET 200SP IM 155-6 MF HF0 < *affected
SiemensSIMATIC ET 200SP IM 155-6 PN HA (incl. SIPLUS variants)0 < V1.3affected
SiemensSIMATIC ET 200SP IM 155-6 PN R10 < V6.0.1affected
SiemensSIMATIC ET 200SP IM 155-6 PN/2 HFV4.2.0 < V4.2.5affected
SiemensSIMATIC ET 200SP IM 155-6 PN/3 HF0 < V4.2.2affected
SiemensSIMATIC PN/MF Coupler0 < *affected
SiemensSIMATIC PN/PN Coupler0 < V6.0.0affected
SiemensSIPLUS ET 200MP IM 155-5 PN HFV4.2.0 < *affected
SiemensSIPLUS ET 200MP IM 155-5 PN HFV4.2.0 < *affected
SiemensSIPLUS ET 200MP IM 155-5 PN HF T1 RAILV4.2.0 < *affected
SiemensSIPLUS ET 200SP IM 155-6 PN HFV4.2.0 < V4.2.5affected
SiemensSIPLUS ET 200SP IM 155-6 PN HFV4.2.0 < V4.2.5affected
SiemensSIPLUS ET 200SP IM 155-6 PN HF T1 RAILV4.2.0 < V4.2.5affected
SiemensSIPLUS ET 200SP IM 155-6 PN HF TX RAILV4.2.0 < V4.2.5affected
SiemensSIPLUS NET PN/PN Coupler0 < V6.0.0affected

Weaknesses

  • CWE-400: CWE-400: Uncontrolled Resource Consumption

ADP Enrichment

CISA ADP Vulnrichment

  • SSVC:
  • Exploitation: none
    • Automatable: yes
    • Technical Impact: partial

References