CVE-2024-43647
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H/E:P/RL:T/RC:C
Summary
A vulnerability has been identified in SIMATIC S7-200 SMART CPU CR40 (6ES7288-1CR40-0AA0) (All versions), SIMATIC S7-200 SMART CPU CR60 (6ES7288-1CR60-0AA0) (All versions), SIMATIC S7-200 SMART CPU SR20 (6ES7288-1SR20-0AA0) (All versions), SIMATIC S7-200 SMART CPU SR20 (6ES7288-1SR20-0AA1) (All versions), SIMATIC S7-200 SMART CPU SR30 (6ES7288-1SR30-0AA0) (All versions), SIMATIC S7-200 SMART CPU SR30 (6ES7288-1SR30-0AA1) (All versions), SIMATIC S7-200 SMART CPU SR40 (6ES7288-1SR40-0AA0) (All versions), SIMATIC S7-200 SMART CPU SR40 (6ES7288-1SR40-0AA1) (All versions), SIMATIC S7-200 SMART CPU SR60 (6ES7288-1SR60-0AA0) (All versions), SIMATIC S7-200 SMART CPU SR60 (6ES7288-1SR60-0AA1) (All versions), SIMATIC S7-200 SMART CPU ST20 (6ES7288-1ST20-0AA0) (All versions), SIMATIC S7-200 SMART CPU ST20 (6ES7288-1ST20-0AA1) (All versions), SIMATIC S7-200 SMART CPU ST30 (6ES7288-1ST30-0AA0) (All versions), SIMATIC S7-200 SMART CPU ST30 (6ES7288-1ST30-0AA1) (All versions), SIMATIC S7-200 SMART CPU ST40 (6ES7288-1ST40-0AA0) (All versions), SIMATIC S7-200 SMART CPU ST40 (6ES7288-1ST40-0AA1) (All versions), SIMATIC S7-200 SMART CPU ST60 (6ES7288-1ST60-0AA0) (All versions), SIMATIC S7-200 SMART CPU ST60 (6ES7288-1ST60-0AA1) (All versions). Affected devices do not properly handle TCP packets with an incorrect structure. This could allow an unauthenticated remote attacker to cause a denial of service condition. To restore normal operations, the network cable of the device needs to be unplugged and re-plugged.
Affected Software
| Vendor | Product | Version Range | Status |
|---|---|---|---|
| Siemens | SIMATIC S7-200 SMART CPU CR40 | 0 < * | affected |
| Siemens | SIMATIC S7-200 SMART CPU CR60 | 0 < * | affected |
| Siemens | SIMATIC S7-200 SMART CPU SR20 | 0 < * | affected |
| Siemens | SIMATIC S7-200 SMART CPU SR20 | 0 < * | affected |
| Siemens | SIMATIC S7-200 SMART CPU SR30 | 0 < * | affected |
| Siemens | SIMATIC S7-200 SMART CPU SR30 | 0 < * | affected |
| Siemens | SIMATIC S7-200 SMART CPU SR40 | 0 < * | affected |
| Siemens | SIMATIC S7-200 SMART CPU SR40 | 0 < * | affected |
| Siemens | SIMATIC S7-200 SMART CPU SR60 | 0 < * | affected |
| Siemens | SIMATIC S7-200 SMART CPU SR60 | 0 < * | affected |
| Siemens | SIMATIC S7-200 SMART CPU ST20 | 0 < * | affected |
| Siemens | SIMATIC S7-200 SMART CPU ST20 | 0 < * | affected |
| Siemens | SIMATIC S7-200 SMART CPU ST30 | 0 < * | affected |
| Siemens | SIMATIC S7-200 SMART CPU ST30 | 0 < * | affected |
| Siemens | SIMATIC S7-200 SMART CPU ST40 | 0 < * | affected |
| Siemens | SIMATIC S7-200 SMART CPU ST40 | 0 < * | affected |
| Siemens | SIMATIC S7-200 SMART CPU ST60 | 0 < * | affected |
| Siemens | SIMATIC S7-200 SMART CPU ST60 | 0 < * | affected |
Weaknesses
- CWE-400: CWE-400: Uncontrolled Resource Consumption
ADP Enrichment
CISA ADP Vulnrichment
- SSVC:
- Exploitation: none
- Automatable: yes
- Technical Impact: partial
References
Feedback
Was this page helpful?
Glad to hear it! Please tell us how we can improve.