CVE-2023-22803
7.5
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
Summary
LS ELECTRIC XBC-DN32U with operating system version 01.80 is missing authentication to perform critical functions to the PLC. This could allow an attacker to change the PLC's mode arbitrarily.
Affected Software
| Vendor | Product | Version Range | Status |
|---|---|---|---|
| LS Electric | XBC-DN32U | Operating System Version 01.80 | affected |
Weaknesses
- CWE-306: CWE-306 Missing Authentication for Critical Function
Workarounds
LS ELECTRIC is developing mitigations (to be released tentatively by the end of 2023) and recommends users follow the provided workarounds to reduce the risk of exploitation:
- Restrict communication to the PLC to only trusted IP addresses and trusted devices by enabling the “Host Table” option in the configuration window of the PLC.
ADP Enrichment
CVE Program Container
Additional References
CISA ADP Vulnrichment
- SSVC:
- Exploitation: none
- Automatable: yes
- Technical Impact: partial
References
Feedback