CVE-2023-2186
8.2
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:H
Summary
On Triangle MicroWorks' SCADA Data Gateway version <= v5.01.03, an unauthenticated attacker can send a specially crafted broadcast message including format string characters to the SCADA Data Gateway to perform unrestricted memory reads.An unauthenticated user can use this format string vulnerability to repeatedly crash the GTWWebMonitor.exe process to DoS the Web Monitor. Furthermore, an authenticated user can leverage this vulnerability to leak memory from the GTWWebMonitor.exe process. This could be leveraged in an exploit chain to gain code execution.
Affected Software
| Vendor | Product | Version Range | Status |
|---|---|---|---|
| Triangle MicroWorks | SCADA Data Gateway | 5.01.03 | affected |
Weaknesses
- CWE-134: CWE-134 Use of Externally-Controlled Format String
ADP Enrichment
CVE Program Container
Additional References
- https://www.trellix.com/en-us/about/newsroom/stories/research/industrial-and-manufacturing-cves.html
CISA ADP Vulnrichment
- SSVC:
- Exploitation: none
- Automatable: yes
- Technical Impact: partial
References
- https://www.trellix.com/en-us/about/newsroom/stories/research/industrial-and-manufacturing-cves.html
Feedback