CVE-2023-2071
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
Summary
Rockwell Automation FactoryTalk View Machine Edition on the PanelView Plus, improperly verifies user’s input, which allows unauthenticated attacker to achieve remote code executed via crafted malicious packets. The device has the functionality, through a CIP class, to execute exported functions from libraries. There is a routine that restricts it to execute specific functions from two dynamic link library files. By using a CIP class, an attacker can upload a self-made library to the device which allows the attacker to bypass the security check and execute any code written in the function.
Affected Software
| Vendor | Product | Version Range | Status |
|---|---|---|---|
| Rockwell Automation | Fa | <=13.0 | affected |
Weaknesses
- CWE-20: CWE-20 Improper Input Validation
ADP Enrichment
CVE Program Container
Additional References
CISA ADP Vulnrichment
- SSVC:
- Exploitation: none
- Automatable: no
- Technical Impact: partial
References
Feedback
Was this page helpful?
Glad to hear it! Please tell us how we can improve.
Sorry to hear that. Please tell us how we can improve.