CVE-2022-31479
CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:C/C:H/I:H/A:H
Summary
An unauthenticated attacker can update the hostname with a specially crafted name that will allow for shell commands to be executed during the core collection process. This vulnerability impacts products based on HID Mercury Intelligent Controllers LP1501, LP1502, LP2500, LP4502, and EP4502 which contain firmware versions prior to 1.302 for the LP series and 1.296 for the EP series. An attacker with this level of access on the device can monitor all communications sent to and from this device, modify onboard relays, change configuration files, or cause the device to become unstable. The injected commands only get executed during start up or when unsafe calls regarding the hostname are used. This allows the attacker to gain remote access to the device and can make their persistence permanent by modifying the filesystem.
Affected Software
| Vendor | Product | Version Range | Status |
|---|---|---|---|
| LenelS2 | LNL-X2210 | ALL < 1.302 | affected |
| LenelS2 | LNL-X2220 | ALL < 1.302 | affected |
| LenelS2 | LNL-X3300 | ALL < 1.302 | affected |
| LenelS2 | LNL-X4420 | ALL < 1.302 | affected |
| LenelS2 | LNL-4420 | ALL < 1.296 | affected |
| LenelS2 | S2-LP-1501 | ALL < 1.302 | affected |
| LenelS2 | S2-LP-1502 | ALL < 1.302 | affected |
| LenelS2 | S2-LP-2500 | ALL < 1.302 | affected |
| LenelS2 | S2-LP-4502 | ALL < 1.302 | affected |
| HID Mercury | LP1501 | ALL < 1.302 | affected |
| HID Mercury | LP1502 | ALL < 1.302 | affected |
| HID Mercury | LP2500 | ALL < 1.302 | affected |
| HID Mercury | LP4502 | ALL < 1.302 | affected |
| HID Mercury | EP4502 | ALL < 1.296 | affected |
Weaknesses
- CWE-693: CWE-693 Protection Mechanism Failure
Workarounds
Disable the controller's Web Server.
When the controller is configured to disable web access, you cannot remotely login into the controller’s web page.
- Login to controller web pages
- Go to “Users” Tab
- Near bottom of the Users page, check option to “Disable Web Server”
- Then select “Submit” at the bottom of the page
- Then select “Apply Settings” tab
- And on that page, select button “Apply Settings, Reboot” The Controller will apply the new setting and reboot. Web login will be disabled until switch 1 is physically turned ON, on the controller.
ADP Enrichment
CVE Program Container
Additional References
References
Feedback
Was this page helpful?
Glad to hear it! Please tell us how we can improve.
Sorry to hear that. Please tell us how we can improve.