CVE-2022-0369
CVSS:3.0/AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H
Summary
Triangle MicroWorks SCADA Data Gateway Restore Workspace Directory Traversal Remote Code Execution Vulnerability. This vulnerability allows remote attackers to execute arbitrary code on affected installations of Triangle MicroWorks SCADA Data Gateway. Although authentication is required to exploit this vulnerability, the existing authentication mechanism can be bypassed.
The specific flaw exists within the Restore Workspace feature. The issue results from the lack of proper validation of a user-supplied path prior to using it in file operations. An attacker can leverage this vulnerability to execute code in the context of SYSTEM. Was ZDI-CAN-17227.
Affected Software
| Vendor | Product | Version Range | Status |
|---|---|---|---|
| Triangle MicroWorks | SCADA Data Gateway | 5.01.01 | affected |
Weaknesses
- CWE-22: CWE-22: Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal')
ADP Enrichment
CISA ADP Vulnrichment
- SSVC:
- Exploitation: none
- Automatable: no
- Technical Impact: total
CVE Program Container