CVE-2021-32986
9.8
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
Summary
After Automation Direct CLICK PLC CPU Modules: C0-1x CPUs with firmware prior to v3.00 is unlocked by an authorized user, the unlocked state does not timeout. If the programming software is interrupted, the PLC remains unlocked. All subsequent programming connections are allowed without authorization. The PLC is only relocked by a power cycle, or when the programming software disconnects correctly.
Affected Software
| Vendor | Product | Version Range | Status |
|---|---|---|---|
| Automation Direct | CLICK PLC CPU Modules: C0-1x CPUs | unspecified < 3.00 | affected |
Weaknesses
- CWE-288: CWE-288: Authentication Bypass Using an Alternate Path or Channel
ADP Enrichment
CVE Program Container
Additional References
CISA ADP Vulnrichment
- SSVC:
- Exploitation: none
- Automatable: yes
- Technical Impact: total
References