CVE-2021-27428
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
Summary
GE UR IED firmware versions prior to version 8.1x supports upgrading firmware using UR Setup configuration tool – Enervista UR Setup. This UR Setup tool validates the authenticity and integrity of firmware file before uploading the UR IED. An illegitimate user could upgrade firmware without appropriate privileges. The weakness is assessed, and mitigation is implemented in firmware Version 8.10.
Affected Software
| Vendor | Product | Version Range | Status |
|---|---|---|---|
| GE | UR family | unspecified < 8.1x | affected |
Weaknesses
- CWE-434: CWE-434 Unrestricted Upload of File with Dangerous Type
Workarounds
GE recommends protecting UR IED by using network defense-in-depth practices. This includes, but is not limited to, placing UR IED inside the control system network security perimeter, and having access controls, monitoring (such as an Intrusion Detection System), and other mitigating technologies in place.
GE recommends users refer to the UR Deployment guide for secure configuration of UR IED and system.
ADP Enrichment
CVE Program Container
Additional References
- https://www.cisa.gov/uscert/ics/advisories/icsa-21-075-02
- https://www.gegridsolutions.com/Passport/Login.aspx
CISA ADP Vulnrichment
- SSVC:
- Exploitation: none
- Automatable: yes
- Technical Impact: total