CVE-2021-27391
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
Summary
A vulnerability has been identified in APOGEE MBC (PPC) (P2 Ethernet) (All versions >= V2.6.3), APOGEE MEC (PPC) (P2 Ethernet) (All versions >= V2.6.3), APOGEE PXC Compact (BACnet) (All versions < V3.5.3), APOGEE PXC Compact (P2 Ethernet) (All versions >= V2.8), APOGEE PXC Modular (BACnet) (All versions < V3.5.3), APOGEE PXC Modular (P2 Ethernet) (All versions >= V2.8), TALON TC Compact (BACnet) (All versions < V3.5.3), TALON TC Modular (BACnet) (All versions < V3.5.3). The web server of affected devices lacks proper bounds checking when parsing the Host parameter in HTTP requests, which could lead to a buffer overflow. An unauthenticated remote attacker could exploit this vulnerability to execute arbitrary code on the device with root privileges.
Affected Software
| Vendor | Product | Version Range | Status |
|---|---|---|---|
| Siemens | APOGEE MBC (PPC) (P2 Ethernet) | All versions >= V2.6.3 | affected |
| Siemens | APOGEE MEC (PPC) (P2 Ethernet) | All versions >= V2.6.3 | affected |
| Siemens | APOGEE PXC Compact (BACnet) | All versions < V3.5.3 | affected |
| Siemens | APOGEE PXC Compact (P2 Ethernet) | All versions >= V2.8 | affected |
| Siemens | APOGEE PXC Modular (BACnet) | All versions < V3.5.3 | affected |
| Siemens | APOGEE PXC Modular (P2 Ethernet) | All versions >= V2.8 | affected |
| Siemens | TALON TC Compact (BACnet) | All versions < V3.5.3 | affected |
| Siemens | TALON TC Modular (BACnet) | All versions < V3.5.3 | affected |
Weaknesses
- CWE-120: CWE-120: Buffer Copy without Checking Size of Input ('Classic Buffer Overflow')
ADP Enrichment
CVE Program Container
Additional References
CISA ADP Vulnrichment
- SSVC:
- Exploitation: none
- Automatable: yes
- Technical Impact: total