CVE-2018-17924
7.5
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
Summary
Rockwell Automation MicroLogix 1400 Controllers and 1756 ControlLogix Communications Modules An unauthenticated, remote threat actor could send a CIP connection request to an affected device, and upon successful connection, send a new IP configuration to the affected device even if the controller in the system is set to Hard RUN mode. When the affected device accepts this new IP configuration, a loss of communication occurs between the device and the rest of the system as the system traffic is still attempting to communicate with the device via the overwritten IP address.
Affected Software
| Vendor | Product | Version Range | Status |
|---|---|---|---|
| n/a | Rockwell Automation | MicroLogix 1400 Controllers Series A, all versions, Series B, v21.003 and earlier,Series C, v21.003 and earlier, 1756 ControlLogix EtherNet/IP Communications Modules 1756-ENBT, all versions, 1756-EWEB Series A, all versions Series B, all versions, 1756-EN2F Series A, all versions, Series B, all versions, Series C, v10.10 and earlier, 1756-EN2T, Series A, all versions, Series B, all versions, Series C, all versions, Series D, v10.10 and earlier, 1756-EN2TR, Series A, all versions, Series B, all versions, Series C, v10.10 and earlier, 1756-EN3TR, Series A, all versions, Series B, v10.10 and earlier. | affected |
Weaknesses
- CWE-306: MISSING AUTHENTICATION FOR CRITICAL FUNCTION CWE-306
ADP Enrichment
CVE Program Container
Additional References
CISA ADP Vulnrichment
- SSVC:
- Exploitation: none
- Automatable: yes
- Technical Impact: partial
References
Feedback
Was this page helpful?
Glad to hear it! Please tell us how we can improve.