CVE-2018-13815
N/A
Summary
A vulnerability has been identified in SIMATIC S7-1200 (All versions), SIMATIC S7-1500 (All Versions < V2.6). An attacker could exhaust the available connection pool of an affected device by opening a sufficient number of connections to the device. Successful exploitation requires an attacker to be able to send packets to port 102/tcp of the affected device. No user interaction and no user privileges are required to exploit the vulnerability. The vulnerability, if exploited, could cause a Denial-of-Service condition impacting the availability of the system. At the time of advisory publication no public exploitation of this vulnerability was known.
Affected Software
| Vendor | Product | Version Range | Status |
|---|---|---|---|
| Siemens AG | SIMATIC S7-1200, SIMATIC S7-1500 | SIMATIC S7-1200 : All versions | affected |
| Siemens AG | SIMATIC S7-1200, SIMATIC S7-1500 | SIMATIC S7-1500 : All Versions < V2.6 | affected |
Weaknesses
- CWE-410: CWE-410: Insufficient Resource Pool
ADP Enrichment
CVE Program Container
Additional References
- http://www.securityfocus.com/bid/105928
- https://cert-portal.siemens.com/productcert/pdf/ssa-584286.pdf
References
- http://www.securityfocus.com/bid/105928
- https://cert-portal.siemens.com/productcert/pdf/ssa-584286.pdf
Feedback
Was this page helpful?
Glad to hear it! Please tell us how we can improve.
Sorry to hear that. Please tell us how we can improve.